POTTER & BRUMFIELD W58 series PUSH TO RESET ONLY THERMAL CIRCUIT BREAKER FEATURES · 0.5A to 35A ratings. · Cannot be manually tripped. · Button extends for visual trip indication. · Push button to reset breaker. · Termination is screw or .250" QC. Shock: Withstands to 10g. Calibration: Will continuously carry 100% of rating. It may trip between 101% and 145%, but must trip at 145% of rating at +25C. Dielectric Strength: Over 1,500 volts RMS. Maximum Operating Voltages: 50VDC; 250VAC. Interrupt Capacity: 2,000A at 50VDC (0.5 - 35A models). 1,000A at 250VAC (0.5 - 35A models). Note: 30 and 35A models not UL or CSA Resettable Overload Capacity: Ten times rated current. Endurance Cycling: Over 1,000 cycles at 200% of rated load. Vibration: Withstands to 10g at 10-55Hz. Approx Weight: Less than 1 1/2oz (42.5g). (approx. 46K .jpg @ 780 pixels wide). BUILD YOUR OWN PART NUMBER: A 70K graphic (jpg) of Ordering Information. This information will 'build' a part number from a list of available specifications. |
Call: 414-327-1555 Fax : 414-327-0577 Email: iebyross@yahoo.com Catalog, Quote, Availability. © 2011 SYNsCON © 2011 Industrial Electronics Corp. of Wisconsin |