Call:
POTTER & BRUMFIELD W58 series PUSH TO RESET ONLY THERMAL CIRCUIT BREAKER FEATURES · 0.5A to 35A ratings. · Cannot be manually tripped. · Button extends for visual trip indication. · Push button to reset breaker. · Termination is screw or .250" QC.
Shock: Withstands to 10g.
Calibration: Will continuously carry 100% of rating.
It may trip between 101% and 145%, but
must trip at 145% of rating at +25C.
Dielectric Strength: Over 1,500 volts RMS.
Maximum Operating Voltages: 50VDC; 250VAC.
Interrupt Capacity: 2,000A at 50VDC (0.5 - 35A models).
1,000A at 250VAC (0.5 - 35A models).
Note: 30 and 35A models not UL or CSA
Resettable Overload Capacity: Ten times rated current.
Endurance Cycling: Over 1,000 cycles at 200% of rated load. Vibration: Withstands to 10g at 10-55Hz. Approx Weight: Less than 1 1/2oz (42.5g). (approx. 46K .jpg @ 780 pixels wide). BUILD YOUR OWN PART NUMBER: A 70K graphic (jpg) of Ordering Information. This information will 'build' a part number from a list of available specifications. |
![]() |
Call: (414) 276-1212 (414) 276-9778 (FAX) (800) 242-7204 (within Wisconsin) Email: indelect@execpc.com Catalog, Quote, Availability. © 1998 TnT Web Design © 1998 Industrial Electronics Corp. of Wisconsin |