SDAS-O1 series
1.5 TO 15 AMP AC CURRENT SENSOR
· Zero insertion loss
· Inductive coupling to power line
· Choice of modes
- Adjustable overcurrent sensor
- Adjustable undercurrent sensor
· Solid state sensing circuit
· 1 Form C (SPDT) or 2 Form C (DPDT) internal relay
SENSING MODES:
Overcurrent sensor - Detects a current in excess of
the value determined by the potentiometer setting. A built-in
time delay, 200 ms, minimum, allows for normal starting and surge
currents. Actual time delay is dependent upon potentiometer setting
and magnitude of overcurrent. Any overcurrent lasting longer than
this causes the internal relay of the SDAS01 to energize. The
relay will remain energized until sensor control voltage is removed,
even if the overcurrent ceases to exist.
Undercurrent sensor - Reacts to a complete loss of
sense current, or any current of less than the potentiometer setting.
Upon application of sensor control voltage, there is a nominal
350ms delay during which time power line current must begin. This
delay gives line components time to turn on. If, at the end of
the delay, sense current should decrease to less than the potentiometer
setting of the SDAS-O1 and remain there for approximately 350
ms, the internal relay of the SDAS-O1 will energize. It will remain
energized until either sense control current again exceeds the
potentiometer setting, or until sensor control voltage is removed.
ENGINEERING DATA:
Control Voltage: 24VAC 50/60 Hz./DC +/- 10%.
Sense-Current Range: 1.5 to 15 amps AC.
Internal Relay Contact Data:
1 Form C (SPDT) type (code X1): 5A @ 28VDC or 2.5A @ 120VAC, res.
2 Form C (DPDT) type (code Y2): 2A @ 28VDC or 1A @ 120VAC, res.
Set Point Variation: +/- 25% over operating temperature range.
Time Delay:
Overcurrent sensor: 200 ms, min., after beginning of
overcurrent. Actual delay is dependent upon potentiometer setting
and magnitude of overcurrent (see Figure 1).
Undercurrent sensor: 350 ms, typ.; 200 ms, min., from beginning
of undercurrent after control voltage is applied.
Power Requirement: 1.7W or 1.7VA @ 24VAC.
Temperature Range: Storage: -40 C to +85 C.
Operating: -25 C to +70 C.
Enclosure: Plastic dust cover.
Mounting: Bracket, socket or printed circuit board options.
For sockets see KUP 3 pole sockets.
Weight: 3.17 oz. (90 g) approximately.
ORDERING INFORMATION:
UNDERCURRENT SENSORS
Part Number Contacts Mounting
SDAS-O1-7Y2B1024 DPDT, 2A DC/1A AC Bracket
SDAS-01-7Y2S1024 DPDT, 2A DC/1A AC Socket
SDAS-01-7Y2P1024 DPDT, 2A DC/1A AC Printed Circuit
SDAS-01-7X1B1024 SPDT, 5A DC/2.5A AC Bracket
SDAS-01-7X1S1024 SPDT, 5A DC/2.5A AC Socket
SDAS-01-7X1P1024 SPDT, 5A DC/2.5A AC Printed Circuit
OVERCURRENT SENSORS
Part Number Contacts Mounting
SDAS-01-8Y2B1024 DPDT, 2A DC/IA AC Bracket
SDAS-01-8Y2S1024 DPDT, 2A DC/1A AC Socket
SDAS-O1-8Y2P1024 DPDT, 2A DC/1A AC Printed Circuit
SDAS-O1-8X1B1024 SPDT, 5A DC/2.5A AC Bracket
SDAS-01-8X1S1024 SPDT, 5A DC/2.5A AC Socket
SDAS-01-8X1P1024 SPDT, 5A DC/2.5A AC Printed Circuit
OUTLINE DIMENSIONS
(approx. 17K .jpg @ 750 pixels wide).
© 1997 Potter & Brumfield Products Division,
Siemens Electromechanical Components, Inc.
 |
POWER RELAYS:
KUHP, S86/87, PM, PRD |
 |
SOLID STATE RELAYS:
SSRT, SSR, SSRD, SSRQ |
 |
SOLID STATE MODULES:
IAC, OAC, IDC, ODC |
 |
 |
TIME DELAY RELAYS:
CND, CNT, CNS, CNM5 |
 |
GENERAL PURPOSE:
R10, KH, KHA, KHAU |
 |
GENERAL PURPOSE:
KRP, KRPA, KR-E, KR-3-H, KA |
 |
 |
GENERAL PURPOSE:
KUP, KUEP, KUIP, KUGP, KUMP, KUP93 |  |
VOLT/CURRENT SENSORS:
CS, SDAS-01 |
 |
CIRCUIT BREAKERS
W28, W58 |
 |
 |
HOME PAGE |
 |
POTTER BRUMFIELD MENU |
Call:
Call: 414-327-1555
Fax : 414-327-0577
Email:
indelect@execpc.com
Catalog, Quote, Availability.
Web Genie: tnt@execpc.com
©1997 Industrial Electronics, Corp
of Wisconsin