POTTER & BRUMFIELD
W28 SERIES CIRCUIT BREAKER
POTTER & BRUMFIELD
W58 series
PUSH TO RESET ONLY
THERMAL CIRCUIT BREAKER
FEATURES
· 0.5A to 35A ratings.
· Cannot be manually tripped.
· Button extends for visual trip indication.
· Push button to reset breaker.
· Termination is screw or .250" QC.
ELECTRICAL DATA @ 25C:
Shock: Withstands to 10g.
Calibration: Will continuously carry 100% of rating.
It may trip between 101% and 145%, but
must trip at 145% of rating at +25C.
Dielectric Strength: Over 1,500 volts RMS.
Maximum Operating Voltages: 50VDC; 250VAC.
Interrupt Capacity: 2,000A at 50VDC (0.5 - 35A models).
1,000A at 250VAC (0.5 - 35A models).
Note: 30 and 35A models not UL or CSA
Resettable Overload Capacity: Ten times rated current.
MECHANICAL/ENVIRONMENTAL DATA:
Endurance Cycling: Over 1,000 cycles at 200% of rated load.
Vibration: Withstands to 10g at 10-55Hz.
Approx Weight: Less than 1 1/2oz (42.5g).
OUTLINE DIMENSIONS
(approx. 46K .jpg @ 780 pixels wide).
BUILD YOUR OWN PART NUMBER:
A 70K graphic (jpg) of Ordering Information.
This information will 'build' a part number from a list of available specifications.
© 1997 Potter & Brumfield Products Division,
Siemens Electromechanical Components, Inc.
 |
POWER RELAYS:
KUHP, S86/87, PM, PRD |
 |
SOLID STATE RELAYS:
SSRT, SSR, SSRD, SSRQ |
 |
SOLID STATE MODULES:
IAC, OAC, IDC, ODC |
 |
 |
TIME DELAY RELAYS:
CND, CNT, CNS, CNM5 |
 |
GENERAL PURPOSE:
R10, KH, KHA, KHAU |
 |
GENERAL PURPOSE:
KRP, KRPA, KR-E, KR-3-H, KA |
 |
 |
GENERAL PURPOSE:
KUP, KUEP, KUIP, KUGP, KUMP, KUP93 |  |
VOLT/CURRENT SENSORS:
CS, SDAS-01 |
 |
CIRCUIT BREAKERS
W28, W58 |
 |
 |
HOME PAGE |
 |
POTTER BRUMFIELD MENU |
Call:
Call: 414-327-1555
Fax : 414-327-0577
Email:
indelect@execpc.com
Catalog, Quote, Availability.
Web Genie: tnt@execpc.com
©1997 Industrial Electronics, Corp
of Wisconsin